DATAFLOW RTU
>>> RTU PROGRAMMER VERSION 3.03 HELP FILE <<<(continued)
Input # 1 # 2 # 3 # 4 # 5 # 6 BATTERY
Tag Name
Initiate Xmit
YES YES NO NO NO NO NO
Type DADDDD A
Invert YES NO NO NO NO NO NO
Threshold / 50 % 10 % 50 % 50 % 50 % 50 % 1.00 V
Dead Zone
Time Delay
5.00 S 0.25 S 0.25 S 0.25 S 0.25 S 0.25 S 0.25 S
The corresponding entries for the output configuration of RTU # 2 would be:
Output Digital 1 Digital 2 Analog 1 Analog 2
Tag Name
Used
YES NO YES NO
Init Condition OPN CLO 0 % 0 %
From ID 1010
From Location INPUT 1 INPUT 1 INPUT 2 INPUT 1
Rcv Check-In 0: 0: 0: 0 0: 0: 0: 0 0: 0: 0: 0 0: 0: 0: 0
Fail-Safe State EFGH
When the RTU is turned on, the outputs will be set to the initial conditions. These values will
remain on the outputs until an incoming message changes the outputs or until a fail-safe
condition is set. Both used and unused outputs can have an initial condition and a fail-safe
state.
This RTU can be programmed to expect a check-in from other units. If this check-in
message is jammed or the other RTU fails to respond, this RTU can set a fail-safe
condition. The value in this field is the amount of time this RTU must go without receiving a
message from the other RTU before it can set its fail-safe state. Each From ID can have
only one receive check-in time. Place this check-in time in the first column which contains
the appropriate From ID.
The letter in the fail-safe state field indicates which fail-safe state will be used upon loss of
signal from the unit listed in From ID. The fail-safe states are listed in the lower right corner
of the system configuration screen.
2.3 Function Keys
The bottom two rows of the RTU input/output configuration screen form the function key
menu. Select an input field and press F1 to display help for the selected field. Press F2 to
display this full help document. Press F10 to return to the RTU system configuration screen.
3.0 RTU SCADA Configuration Screen
The SCADA configuration screen lists four SCADA points which can be stored in the RTU
EEPROM. The function key menu provides access to the full SCADA configuration. SCADA
configuration allows the user to connect one RTU to a supervisory control and data
acquisition program and poll remote RTUs over RF. The SCADA program must use the
MODBUS protocol. The SCADA configuration must reside in the one RTU connected
directly to the SCADA program. That RTU uses the routing information in the SCADA
configuration to send an RF message to the addressed RTU.
D=Digital, A=Analog
( B-9 )